NFPA 72 Chapter 23.10.2 states: “Fire alarm systems used for partial evacuation and relocation shall be designed and installed so that attack by fire within a notification zone shall not impair control and operation of the notification appliances outside that notification zone.” Most, if not all hospitals use partial evacuation or relocation when a fire occurs on a floor.
If a hospital’s written fire response plan relocates occupants to smoke zones on the same floor, then CI cable must be used for notification circuits until they reach their particular smoke zone. Those circuits are usually dedicated to those zones. However, if smoke zones are not used to re-locate occupants from a zone in alarm on that same floor, then NFPA 72 Chapter 23.10.2 allows the NAC circuits serving that floor to be converted back to non-CI once they reach the floor. Therefore, if the NAC circuits originate on that floor, you wouldn’t need CI for the NAC circuits since the whole floor is the evacuation zone.
However, if the method of triggering the NAC panel originates from a different floor, then the circuit that controls the trigger would need to be installed with 2 hour survivability. For example, if you’re using an addressable module to trigger & monitor the NAC panel, the SLC must also originate from the same floor or else it would have to be run in CI before it gets to the floor. The cost of doing that would be astronomical, so if you’re using that method, make sure your SLC starts on the floor or is dedicated to the floor & is in CI until it gets to the floor to avoid violating NFPA 72. Remote data gathering panels per floor work well since they can operate in stand alone mode if you lose network communications.
Gamewell-FCI fire alarm equipment can accommodate any notification scenario utilizing fiber, ethernet, CI cable or THHN. Contact Affiliated Fire Systems for more information on getting your life safety needs met in the most efficient way possible.
Gene Rowe,SET